Victron Discount code: VICT5

Call us 1300 368 331

View CART

SKU: REL100200000 Category:

Anti-islanding relay SPI1021

Product Specifications

SPECIFICATIONS:
POWER SUPPLY (RATED SUPPLY VOLTAGE US): AC/DC 24-270 V, 0/40…70 Hz, <5VADC: 20,4…297 V, AC: 20,4…297 V
RELAY OUTPUT: 2 change-over contacts
MEASURING VOLTAGE:

  • VOLTAGE PHASE-PHASE: AC 15…530 V (< 5 V display 0)
  • SETTING RANGE PHASE-PHASE: AC 15…520 V
  • VOLTAGE PHASE-NEUTRAL: AC 10…310 V (< 5 V display 0)
  • SETTING RANGE PHASE-NEUTRAL: AC 15…300 V
  • MEASUREMENT METHOD: true RMS
  • HYSTERESIS: adjustable1,0…99,9 V
  • MEASUREMENT ACCURACY (WITH NEUTRAL): ±0,6% of measured value
  • MEASUREMENT ACCURACY (WITHOUT NEUTRAL): ±0,8% of measured value
  • ACCURACY OF DISPLAY: >100V: ±1 digit (resolution 1 V); <100V: ±1 digit (resolution 0,1 V)
  • MEASUREMENT FUNCTIONS: 3-phase with / without neutral, single phase
  • SWITCHING-DELAY (dAL): adjustable 0,05 (± 15ms)…130,0 s
  • SWITCHING-BACK-DELAY (doF): adjustable 0 (= 40ms)…999 s

MEASURING FREQUENCY:

  • MEASUREMENT RANGE : 40….70 Hz
  • SETTING RANGE: 45,00…65,00 Hz
  • HYSTERESIS: 0,05…10,00 Hz
  • MEASUREMENT ACCURACY: ± 0,01 Hz ± 1 digit
  • SWITCHING-DELAY (dAL): adjustable 0,05 (± 15ms)…130,0 s
  • SWITCHING-BACK-DELAY (doF): adjustable 0 (= 40ms)…999 s

VECTOR-SHIFT:

  • MEASUREMENT RANGE: ..45,0°
  • MEASUREMENT RANGE: 2,0…20,0°
  • SWITCHING-DELAY (dAL): < 50 ms
  • SWITCHING-BACK-DELAY (doF): adjustable 3…240 s
  • DELAY AT US ON: adjustable 2…20 s

DIGITAL INPUTS (INx):

  • SWITCHING VOLTAGE + U: DC 15…37 V
  • CURRENT INx: > 3 mA

INPUT FEEDBACK CONTACT:

  • SWITCHING VOLTAGE Y0…Y1: DC 15…35 V
  • CURRENT Y1: > 3 mA
  • SWITCHING TIME CONNECTED SWITCHES: adjustable 0,5…99,0 s

WIRING CONNECTION SINGLE STRAND: 1 x 4 mm2
ATTACHMENT: DIN-rail 35 mm according to EN 60 715 or screws M4
FINELY STRANDED WITH WIRE END FERULE: 1 x 2,5 mm2
DIMENTIONS (H x W x D): 90 x 105 x 69 mm
WEIGHT: 0.25kg

See full description

$784.00

Anti-islanding relay SPI1021

Product Description

Victron Energy’s Anti-Islanding Relay SPI1021 can be used to monitor the voltage and frequency in plants for own generation of electricity. It fulfills the requirements of CEI 0-21.3 selectable programs allow measuring 3 phases to neutral (4-wire mode), 3 phases phase-phase (3-wire mode) and single phase to neutral (2-wire).

The SPI1021 can monitor all de-centralized power, photovoltaic, wind or thermal plants, that feed in the low voltage and medium voltage grid. In applications with possible asymmetry >6 kVA, power balance has to be monitored extra. With the integrated certified self-test, the device can be used in plants < 6kVA.All limits are preset according to CEI 0-21.

They can be changed if required and be protected with a code and/or a seal. A counter for alarms and standbys stores the last 100 events with reason and elapsed time. In addition, the time the SPI1021 has interrupted the plant is recorded.

All values can be displayed at the device and give the operator valuable information about the availability of the plant. When the device has been installed, a self-test starts automatically. The self-test can be re-peated when required.

All values of the test are stored and can be read out at the display.

  • Monitoring of under- and overvoltage 15-520 V
  • Measuring of 3 phase with or without neutral or single phase
  • Monitoring of over- and underfrequency 45-65 Hz
  • Monitoring of quality of voltage (10-minutes-average)Monitoring of vector-shift (connectible)Input IN2 for selection of frequency window
  • Input In3 for selection of mode transitory or definitive
  • Input Y0/Y1 for monitoring function of connected switch (automatic detection of nc/no)
  • Relay K2 picks up (on time <500 ms) only at failure at switch connected to K1
  • 2 restarts at switch-on error of connected switch
  • Self-test with storing of values
  • Switching delays adjustable 0,05…130 s
  • Switching-back-delays adjustable 0…999 s
  • Different switching time according to type of alarm and selected mode
  • Switch-on delay 300 s (adjustable)All parameters preset according to CEI 0-21Alarm counter for 100 alarms with value. Reason and elapsed time
  • Recording of added time of alarms
  • Input for standby (off time <50ms) with counter and recording of time
  • Simulation for testing
  • Sealing, all parameters can be read out while sealed
  • Easy installation and programming with 3 preset programs
  • Supply-voltage AC/DC 24-270 V
  • Housing for DIN-rail-mount, 105 mm wide, mounting height 70 mm

Additional Information